| S12UPS-3.0/12DC | Ibex Manufacturing, Inc. | |
|
12VDC Input/Output UPS with 5Ah 12V SLA Battery. -40C to +60C Operation. |
|
Block Diagram Operation Manual Electrical Specs. Mechanical Info. |
||||||
|
Charger Characteristics: The following graph shows the typical charger output current at a 13.7V charger output voltage versus the unit's input voltage. The graph shows that, when the input voltage is between 5V and 10.8V, the charger still supplies current to the battery. This reduces the drain on the battery (which now supplies the unit's output current). If the unit's output current load is less than what the charger can supply, the battery never discharges. If the load is greater than this, the battery makes up the difference - but still discharges more slowly than without the charger's contribution. Below 5V input, the charger shuts down and the battery supplies all of the unit's output current. If the unit's input voltage is above 10.8V, then the input voltage supplies all of the unit's output current. All of the charger's output then goes to recharge/maintain the battery (as needed).
| |||||||
|
Battery Life in Standby Service: The following graph shows the expected 4 to 5 year life of a battery that is never subjected discharge/charge cycles.
| |||||||
|
Battery Life in Cyclic Service: The following graph shows the reduced battery life when subjected to discharge/charge cycles.
| |||||||
|
Battery Shelf Life: When storing the UPS, the mating connector is normally disconnected. The causes the unit to disconnect the battery from the internal circuitry. The battery then slowly discharges only from its own leakage current.
| |||||||
|
|
|||||||